CVE-2017-7901

high

Description

A Predictable Value Range from Previous Values issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1100 programmable-logic controllers 1763-L16AWA, Series A and B, Version 16.00 and prior versions; 1763-L16BBB, Series A and B, Version 16.00 and prior versions; 1763-L16BWA, Series A and B, Version 16.00 and prior versions; and 1763-L16DWD, Series A and B, Version 16.00 and prior versions and Allen-Bradley MicroLogix 1400 programmable logic controllers 1766-L32AWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWAA, Series A and B, Version 16.00 and prior versions; 1766-L32BXB, Series A and B, Version 16.00 and prior versions; 1766-L32BXBA, Series A and B, Version 16.00 and prior versions; and 1766-L32AWAA, Series A and B, Version 16.00 and prior versions. Insufficiently random TCP initial sequence numbers are generated, which may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections, resulting in a denial of service for the target device.

References

https://ics-cert.us-cert.gov/advisories/ICSA-17-115-04

http://www.securitytracker.com/id/1038546

Details

Source: Mitre, NVD

Published: 2017-06-30

Updated: 2024-11-21

Risk Information

CVSS v2

Base Score: 9

Vector: CVSS2#AV:N/AC:L/Au:N/C:P/I:P/A:C

Severity: High

CVSS v3

Base Score: 8.6

Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:H