CVE-2019-18336

high

Description

A vulnerability has been identified in SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V3.X.17), SIMATIC TDC CP51M1 (All versions < V1.1.8), SIMATIC TDC CPU555 (All versions < V1.1.1), SINUMERIK 840D sl (All versions < V4.8.6), SINUMERIK 840D sl (All versions < V4.94). Specially crafted packets sent to port 102/tcp (Profinet) could cause the affected device to go into defect mode. A restart is required in order to recover the system. Successful exploitation requires an attacker to have network access to port 102/tcp, with no authentication. No user interation is required. At the time of advisory publication no public exploitation of this security vulnerability was known.

References

https://cert-portal.siemens.com/productcert/pdf/ssa-508982.pdf

Details

Source: Mitre, NVD

Published: 2020-03-10

Updated: 2020-09-29

Risk Information

CVSS v2

Base Score: 7.8

Vector: CVSS2#AV:N/AC:L/Au:N/C:N/I:N/A:C

Severity: High

CVSS v3

Base Score: 7.5

Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Severity: High