CVE-2020-25178

high

Description

ISaGRAF Workbench communicates with Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x using TCP/IP. This communication protocol provides various file system operations, as well as the uploading of applications. Data is transferred over this protocol unencrypted, which could allow a remote unauthenticated attacker to upload, read, and delete files.

References

https://www.xylem.com/siteassets/about-xylem/cybersecurity/advisories/xylem-multismart-rockwell-isagraf.pdf

https://www.cisa.gov/uscert/ics/advisories/icsa-20-280-01

https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1131699

https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-159-04

Details

Source: Mitre, NVD

Published: 2022-03-18

Updated: 2022-04-04

Risk Information

CVSS v2

Base Score: 9.3

Vector: CVSS2#AV:N/AC:M/Au:N/C:C/I:C/A:C

Severity: High

CVSS v3

Base Score: 8.8

Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H

Severity: High