CVE-2021-35533

high

Description

Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions).

References

https://search.abb.com/library/Download.aspx?DocumentID=8DBD000063&LanguageCode=en&DocumentPartId=&Action=Launch

Details

Source: Mitre, NVD

Published: 2021-11-26

Updated: 2023-05-16

Risk Information

CVSS v2

Base Score: 7.1

Vector: CVSS2#AV:N/AC:M/Au:N/C:N/I:N/A:C

Severity: High

CVSS v3

Base Score: 7.5

Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Severity: High