CVE-2022-29965

medium

Description

The Emerson DeltaV Distributed Control System (DCS) controllers and IO cards through 2022-04-29 misuse passwords. Access to privileged operations on the maintenance port TELNET interface (23/TCP) on M-series and SIS (CSLS/LSNB/LSNG) nodes is controlled by means of utility passwords. These passwords are generated using a deterministic, insecure algorithm using a single seed value composed of a day/hour/minute timestamp with less than 16 bits of entropy. The seed value is fed through a lookup table and a series of permutation operations resulting in three different four-character passwords corresponding to different privilege levels. An attacker can easily reconstruct these passwords and thus gain access to privileged maintenance operations. NOTE: this is different from CVE-2014-2350.

References

https://www.forescout.com/blog/

https://www.cisa.gov/uscert/ics/advisories/icsa-22-181-03

Details

Source: Mitre, NVD

Published: 2022-07-26

Updated: 2023-01-24

Risk Information

CVSS v2

Base Score: 4.6

Vector: CVSS2#AV:L/AC:L/Au:S/C:C/I:N/A:N

Severity: Medium

CVSS v3

Base Score: 5.5

Vector: CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N

Severity: Medium