CVE-2022-4608

high

Description

A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.

References

https://publisher.hitachienergy.com/preview?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch

Details

Source: Mitre, NVD

Published: 2023-07-26

Updated: 2024-09-25

Risk Information

CVSS v2

Base Score: 7.8

Vector: CVSS2#AV:N/AC:L/Au:N/C:N/I:N/A:C

Severity: High

CVSS v3

Base Score: 7.5

Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Severity: High