Improper Authentication vulnerability in the mobile monitoring feature of ICONICS GENESIS64 versions 10.97 to 10.97.2, Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.2 and Mitsubishi Electric MC Works64 all versions allows a remote unauthenticated attacker to bypass proper authentication and log in to the system when all of the following conditions are met: * Active Directory is used in the security setting. * “Automatic log in” option is enabled in the security setting. * The IcoAnyGlass IIS Application Pool is running under an Active Directory Domain Account. * The IcoAnyGlass IIS Application Pool account is included in GENESIS64TM and MC Works64 Security and has permission to log in.
https://www.cisa.gov/news-events/ics-advisories/icsa-24-184-03
https://www.mitsubishielectric.com/en/psirt/vulnerability/pdf/2024-004_en.pdf