Rockwell Automation MicroLogix Controllers and RSLogix 500 Software Use of Hard-Coded Cryptographic Key (CVE-2020-6990)

critical Tenable OT Security Plugin ID 500369

Synopsis

The remote OT asset is affected by a vulnerability.

Description

Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic key utilized to help protect the account password is hard coded into the RSLogix 500 binary file. An attacker could identify cryptographic keys and use it for further cryptographic attacks that could ultimately lead to a remote attacker gaining unauthorized access to the controller.

This plugin only works with Tenable.ot. Please visit https://www.tenable.com/products/tenable-ot for more information.

Solution

The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original can be found at CISA.gov.

For MicroLogix 1400 series B controllers, Rockwell recommends affected users apply FRN 21.002 or later for MicroLogix 1400 Series B devices and use the enhanced password security feature.

Rockwell Automation reports that there are currently no mitigations for MicroLogix 1400 series A controllers or MicroLogix 1100 controllers.

For RSLogix 500 software, Rockwell Automation recommends affected users apply v11 or later and use in conjunction with applied FRN 21.001 or later for Micrologix 1400 Series B devices. Other configurations do not have direct mitigations.

See Also

https://www.us-cert.gov/ics/advisories/icsa-20-070-06

http://www.nessus.org/u?d3665415

Plugin Details

Severity: Critical

ID: 500369

Version: 1.9

Type: remote

Family: Tenable.ot

Published: 2/7/2022

Updated: 9/4/2024

Supported Sensors: Tenable OT Security

Risk Information

VPR

Risk Factor: Medium

Score: 5.9

CVSS v2

Risk Factor: Critical

Base Score: 10

Temporal Score: 7.4

Vector: CVSS2#AV:N/AC:L/Au:N/C:C/I:C/A:C

CVSS Score Source: CVE-2020-6990

CVSS v3

Risk Factor: Critical

Base Score: 9.8

Temporal Score: 8.5

Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Temporal Vector: CVSS:3.0/E:U/RL:O/RC:C

Vulnerability Information

CPE: cpe:/o:rockwellautomation:micrologix_1400_a_firmware, cpe:/o:rockwellautomation:micrologix_1100_firmware, cpe:/o:rockwellautomation:micrologix_1400_b_firmware

Required KB Items: Tenable.ot/Rockwell

Exploit Ease: No known exploits are available

Patch Publication Date: 3/16/2020

Vulnerability Publication Date: 3/16/2020

Reference Information

CVE: CVE-2020-6990

CWE: 798

ICSA: 20-070-06