Siemens SIMATIC CP 1543-1 Improper Input Validation (CVE-2016-8562)

high Tenable OT Security Plugin ID 500605

Synopsis

The remote OT asset is affected by a vulnerability.

Description

A vulnerability has been identified in SIMATIC CP 1543-1 (All versions < V2.0.28), SIPLUS NET CP 1543-1 (All versions < V2.0.28). Under special conditions it was possible to write SNMP variables on port 161/udp which should be read-only and should only be configured with TIA-Portal. A write to these variables could reduce the availability or cause a denial-of-service.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

Solution

The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original can be found at CISA.gov.

Siemens has released updates for the affected products and recommends users update to the latest versions.:

- SIMATIC CP 1543-1: Update to v2.0.28 or later version
- SIPLUS NET CP 1543-1: Update to v2.0.28 or later version

As a general security measure, Siemens strongly recommends protecting network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security, and following the recommendations in the product manuals.

Additional information on industrial security by Siemens can be found at: https://www.siemens.com/industrialsecurity

For more information on this vulnerability and more detailed mitigation instructions, please see Siemens Security Advisory SSA-672373

See Also

https://ics-cert.us-cert.gov/advisories/ICSA-16-327-01

https://cert-portal.siemens.com/productcert/pdf/ssa-672373.pdf

Plugin Details

Severity: High

ID: 500605

Version: 1.10

Type: remote

Family: Tenable.ot

Published: 3/15/2022

Updated: 9/4/2024

Supported Sensors: Tenable OT Security

Risk Information

VPR

Risk Factor: High

Score: 7.4

CVSS v2

Risk Factor: Low

Base Score: 3.5

Temporal Score: 2.9

Vector: CVSS2#AV:N/AC:M/Au:S/C:N/I:N/A:P

CVSS Score Source: CVE-2016-8562

CVSS v3

Risk Factor: High

Base Score: 7.5

Temporal Score: 7

Vector: CVSS:3.0/AV:N/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H

Temporal Vector: CVSS:3.0/E:F/RL:O/RC:C

Vulnerability Information

CPE: cpe:/o:siemens:simatic_cp_1543-1_firmware

Required KB Items: Tenable.ot/Siemens

Exploit Available: true

Exploit Ease: Exploits are available

Patch Publication Date: 11/18/2016

Vulnerability Publication Date: 11/18/2016

CISA Known Exploited Vulnerability Due Dates: 3/24/2022

Reference Information

CVE: CVE-2016-8562

ICSA: 16-327-01