ABB RTU500 Stack-Based Buffer Overflow (CVE-2022-2502)

high Tenable OT Security Plugin ID 501614

Synopsis

The remote OT asset is affected by a vulnerability.

Description

A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature Advanced security' which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

Solution

Refer to the vendor advisory.

See Also

http://www.nessus.org/u?382e4c09

Plugin Details

Severity: High

ID: 501614

Version: 1.2

Type: remote

Family: Tenable.ot

Published: 9/6/2023

Updated: 10/3/2023

Supported Sensors: Tenable OT Security

Risk Information

VPR

Risk Factor: Low

Score: 3.6

CVSS v2

Risk Factor: High

Base Score: 7.8

Temporal Score: 5.8

Vector: CVSS2#AV:N/AC:L/Au:N/C:N/I:N/A:C

CVSS Score Source: CVE-2022-2502

CVSS v3

Risk Factor: High

Base Score: 7.5

Temporal Score: 6.5

Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Temporal Vector: CVSS:3.0/E:U/RL:O/RC:C

Vulnerability Information

CPE: cpe:/o:hitachienergy:rtu500_firmware:13.3.1, cpe:/o:hitachienergy:rtu500_firmware:13.3.2

Required KB Items: Tenable.ot/ABB

Exploit Ease: No known exploits are available

Patch Publication Date: 7/26/2023

Vulnerability Publication Date: 7/26/2023

Reference Information

CVE: CVE-2022-2502

CWE: 20