Siemens SIMATIC S7-1500 Uncontrolled Resource Consumption (CVE-2024-2511)

low Tenable OT Security Plugin ID 502258

Synopsis

The remote OT asset is affected by a vulnerability.

Description

Issue summary: Some non-default TLS server configurations can cause unbounded memory growth when processing TLSv1.3 sessions

Impact summary: An attacker may exploit certain server configurations to trigger unbounded memory growth that would lead to a Denial of Service.

This problem can occur in TLSv1.3 if the non-default SSL_OP_NO_TICKET option is being used (but not if early_data support is also configured and the default anti-replay protection is in use). In this case, under certain conditions, the session cache can get into an incorrect state and it will fail to flush properly as it fills. The session cache will continue to grow in an unbounded manner.

A malicious client could deliberately create the scenario for this failure to force a Denial of Service. It may also happen by accident in normal operation. This issue only affects TLS servers supporting TLSv1.3. It does not affect TLS clients. The FIPS modules in 3.2, 3.1 and 3.0 are not affected by this issue. OpenSSL 1.0.2 is also not affected by this issue.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

Solution

Siemens has identified the following specific workarounds and mitigations that customers can apply to reduce the risk:

- Only build and run applications from trusted sources

Product-specific remediations or mitigations can be found in the section 'Affected Products and Solution' of the vendor advisory.

For more information, see the associated Siemens security advisory in HTML and CSAF.

See Also

https://cert-portal.siemens.com/productcert/html/ssa-265688.html

Plugin Details

Severity: Low

ID: 502258

Version: 1.2

Type: remote

Family: Tenable.ot

Published: 6/3/2024

Updated: 6/4/2024

Supported Sensors: Tenable OT Security

Risk Information

VPR

Risk Factor: Low

Score: 3.6

CVSS v3

Risk Factor: Low

Base Score: 3.7

Temporal Score: 3.4

Vector: CVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:L

Temporal Vector: CVSS:3.0/E:P/RL:O/RC:C

Vulnerability Information

CPE: cpe:/o:siemens:simatic_s7-1500_tm_mfp

Required KB Items: Tenable.ot/Siemens

Exploit Available: true

Exploit Ease: Exploits are available

Vulnerability Publication Date: 4/14/2024

Reference Information

CVE: CVE-2024-2511