Siemens SIMATIC CP Incorrect Authorization (CVE-2024-50310)

high Tenable OT Security Plugin ID 502663

Synopsis

The remote OT asset is affected by a vulnerability.

Description

A vulnerability has been identified in SIMATIC CP 1543-1 V4.0 (6GK7543-1AX10-0XE0) (All versions >= V4.0.44 < V4.0.50). Affected devices do not properly handle authorization. This could allow an unauthenticated remote attacker to gain access to the filesystem.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

Solution

The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original can be found at CISA.gov.

Siemens has identified the following specific workarounds and mitigations that users can apply to reduce risk:

- SIMATIC CP1543-1 V4.0 (6GK7543-1AX10-0XE0): Update to SIMATIC CP1543-1 V4.0.50 or later versions
- Restrict access to Port 8448/tcp to trusted systems only

As a general security measure, Siemens strongly recommends protecting network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens' operational guidelines for industrial security, and following the recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage

For more information see the associated Siemens security advisory SSA-654798 in HTML and CSAF.

See Also

https://cert-portal.siemens.com/productcert/html/ssa-654798.html

https://www.cisa.gov/news-events/ics-advisories/icsa-24-319-11

Plugin Details

Severity: High

ID: 502663

Version: 1.4

Type: remote

Family: Tenable.ot

Published: 11/13/2024

Updated: 12/12/2024

Supported Sensors: Tenable OT Security

Risk Information

VPR

Risk Factor: Low

Score: 3.6

CVSS v2

Risk Factor: High

Base Score: 7.8

Temporal Score: 5.8

Vector: CVSS2#AV:N/AC:L/Au:N/C:C/I:N/A:N

CVSS Score Source: CVE-2024-50310

CVSS v3

Risk Factor: High

Base Score: 7.5

Temporal Score: 6.5

Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

Temporal Vector: CVSS:3.0/E:U/RL:O/RC:C

Vulnerability Information

CPE: cpe:/o:siemens:simatic_cp_1543-1_firmware

Required KB Items: Tenable.ot/Siemens

Exploit Ease: No known exploits are available

Patch Publication Date: 11/12/2024

Vulnerability Publication Date: 11/12/2024

Reference Information

CVE: CVE-2024-50310

CWE: 863

ICSA: 24-319-11