Schneider Electric Modicon M340, MC80, and Momentum Unity M1E Improper Enforcement of Message Integrity During Transmission in a Communication Channel (CVE-2024-8933)

high Tenable OT Security Plugin ID 502689

Synopsis

The remote OT asset is affected by a vulnerability.

Description

A vulnerability exists that could cause retrieval of password hash that could lead to denial of service and loss of confidentiality and integrity of controllers. To be successful, the attacker needs to inject themselves inside the logical network while a valid user uploads or downloads a project file into the controller.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

Solution

The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original can be found at CISA.gov.

Schneider Electric is establishing a remediation plan for all future versions of Modicon M340 that will include a fix for CVE-2024-8933 vulnerability and a mitigation for CVE-2024-8935.

Additionally, Schneider Electric will update this document when the remediation is available. Until then, users should immediately apply the following mitigations to reduce the risk of exploit:

- Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP
- Configure the Access Control List following the recommendations of the user manuals: "Modicon M340 for Ethernet Communications Modules and Processors User Manual" in chapter "Messaging Configuration Parameters"
- Consider use of external firewall devices such as EAGLE40-07 from Belden to establish VPN connections. For more details refer to "Modicon Controller Systems Cybersecurity, User Guide"
- Ensure the M340 CPU is running with the memory protection activated by configuring the input bit to a physical input, for more details refer to the following guideline "Modicon Controller Systems Cybersecurity, User Guide" chapter "Controler Memory Protection"

Schneider Electric is also establishing a remediation plan for all future versions of Modicon MC80 that will include a fix for CVE-2024-8933. Schneider Electric will update this document when the remediation is available. Until then, users should immediately apply the following mitigations to reduce the risk of exploit:

- Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP
- Configure the Access Control List following the recommendations of the user manuals: "MC80 Programmable Logic Controller(PLC), User Manual" in the section "Access Control List (ACL)"
- Consider use of external firewall devices such as EAGLE40-07 from Belden to establish VPN connections. For more details refer to "Modicon Controller Systems Cybersecurity, User Guide"

Schneider Electric is also establishing a remediation plan for all future versions of Modicon Momentum that will include a fix for CVE-2024-8933. Schneider Electric will update this document when the remediation is available. Until then, users should immediately apply the following mitigations to reduce the risk of exploit:

- Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP
- Configure the Access Control List following the recommendations of the user manuals: "Momentum for EcoStruxure™ Control Expert -171CBU78090, 171CBU98090, 171CBU98091 Processors, User Guide" in the section "Controlling Access"
- Consider use of external firewall devices such as EAGLE40-07 from Belden to establish VPN connections. For more details refer to "Modicon Controller Systems Cybersecurity, User Guide"

To ensure you are informed of all updates, including details on affected products and remediation plans, subscribe to Schneider Electric's security notification service here.

General Security RecommendationsSchneider Electric strongly recommend the following industry cybersecurity best practices.

- Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.
- Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.
- Place all controllers in locked cabinets and never leave them in the "Program" mode.
- Never connect programming software to any network other than the network intended for that device.
- Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.
- Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.
- Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.
- When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.

For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.

For more information see the associated Schneider Electric Security Notification SEVD-2024-317-02 in PDF and CSAF.

See Also

http://www.nessus.org/u?1d3b28ca

https://www.cisa.gov/news-events/ics-advisories/icsa-24-326-03

Plugin Details

Severity: High

ID: 502689

Version: 1.3

Type: remote

Family: Tenable.ot

Published: 11/28/2024

Updated: 12/12/2024

Supported Sensors: Tenable OT Security

Risk Information

VPR

Risk Factor: Medium

Score: 5.9

CVSS v3

Risk Factor: High

Base Score: 7.5

Temporal Score: 6.5

Vector: CVSS:3.0/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H

Temporal Vector: CVSS:3.0/E:U/RL:O/RC:C

Vulnerability Information

CPE: cpe:/o:schneider-electric:modicon_mc80, cpe:/o:schneider-electric:modicon_momentum_171cbu78090_firmware, cpe:/o:schneider-electric:modicon_momentum_171cbu98090_firmware, cpe:/o:schneider-electric:modicon_m340, cpe:/o:schneider-electric:modicon_momentum_171cbu98091_firmware

Required KB Items: Tenable.ot/Schneider

Exploit Ease: No known exploits are available

Patch Publication Date: 11/12/2024

Vulnerability Publication Date: 11/12/2024

Reference Information

CVE: CVE-2024-8933

CWE: 924

ICSA: 24-326-03