Siemens SIPROTEC 5 Use of Default Credentials (CVE-2024-54015)

high Tenable OT Security Plugin ID 502863

Synopsis

The remote OT asset is affected by a vulnerability.

Description

Affected devices do not properly validate SNMP GET requests. This could allow an unauthenticated, remote attacker to retrieve sensitive information of the affected devices with SNMPv2 GET requests using default credentials.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

Solution

Siemens has identified the following specific workarounds and mitigations that customers can apply to reduce the risk:

- Restrict access to port 161/udp to trusted IP addresses only
- Disable the SNMP service running in the communication modules, if not used

Product-specific remediations or mitigations can be found in the section Affected Products and Solution. Please follow the General Security Recommendations.

See Also

https://cert-portal.siemens.com/productcert/html/ssa-767615.html

https://www.cisa.gov/news-events/ics-advisories/icsa-25-044-05

Plugin Details

Severity: High

ID: 502863

Version: 1.2

Type: remote

Family: Tenable.ot

Published: 2/20/2025

Updated: 2/21/2025

Supported Sensors: Tenable OT Security

Risk Information

VPR

Risk Factor: Medium

Score: 4.4

CVSS v2

Risk Factor: High

Base Score: 7.8

Temporal Score: 5.8

Vector: CVSS2#AV:N/AC:L/Au:N/C:C/I:N/A:N

CVSS Score Source: CVE-2024-54015

CVSS v3

Risk Factor: High

Base Score: 7.5

Temporal Score: 6.7

Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

Temporal Vector: CVSS:3.0/E:P/RL:O/RC:C

Vulnerability Information

CPE: cpe:/o:siemens:siprotec_5_7sa86_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7ve85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sd87_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sl82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_7sk85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_compact_7sx800_%28cp050%29_firmware, cpe:/o:siemens:siprotec_5_7sk82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_7sj81_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_6md86_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7vu85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7ut86_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_6mu85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7st86_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sd82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_6md85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7ut85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sd86_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sx82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_7vk87_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sj82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_7ke85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7um85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sl87_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sj86_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sx85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sa82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_7ut82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_7sy82_%28cp150%29_firmware, cpe:/o:siemens:siprotec_5_7st85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sj85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sa87_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7ss85_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_6md84_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_6md89_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7ut87_%28cp300%29_firmware, cpe:/o:siemens:siprotec_5_7sl86_%28cp300%29_firmware

Required KB Items: Tenable.ot/Siemens

Exploit Available: true

Exploit Ease: Exploits are available

Patch Publication Date: 2/11/2025

Vulnerability Publication Date: 2/11/2025

Reference Information

CVE: CVE-2024-54015

CWE: 1392

ICSA: 25-044-05