Siemens SIMOCODE Pro V EIP < 1.0.2 DoS

high Nessus Network Monitor Plugin ID 700527

Synopsis

The remote host is running a SIMOCODE Pro V EIP management system that is affected by a Denial-of-Service (DoS) vulnerability.

Description

The remote device is running SIMOCODE Pro V EIP prior to version 1.0.2, and is therefore affected by a vulnerability that could allow remote attackers to conduct a DoS attack by sending specially crafted packets to port 161/udp (SNMP).

Solution

Upgrade SIMOCODE Pro V EIP to version 1.0.2 or higher

See Also

https://cert-portal.siemens.com/productcert/pdf/ssa-141614.pdf

https://ics-cert.us-cert.gov/advisories/ICSA-19-099-01

Plugin Details

Severity: High

ID: 700527

Family: SCADA

Published: 4/10/2019

Updated: 4/10/2019

Risk Information

VPR

Risk Factor: Low

Score: 3.6

CVSS v2

Risk Factor: High

Base Score: 7.8

Temporal Score: 5.8

Vector: CVSS2#AV:N/AC:L/Au:N/C:N/I:N/A:C

CVSS v3

Risk Factor: High

Base Score: 7.5

Temporal Score: 6.5

Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Temporal Vector: CVSS:3.0/E:U/RL:O/RC:C

Vulnerability Information

CPE: cpe:/h:siemens:simocode_pro_v

Patch Publication Date: 4/10/2019

Vulnerability Publication Date: 4/10/2019

Reference Information

CVE: CVE-2017-12741

BID: 101964