Rockwell Automation/Allen-Bradley Ethernet/IP Products Denial of Service

high Nessus Network Monitor Plugin ID 720000

Synopsis

Rockwell Automation EtherNet/IP products allow remote attackers to cause a denial of service condition.

Description

Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400 allow remote attackers to cause a denial of service (control and communication outage) via a CIP message that specifies a logic-execution stop and fault.

Solution

Rockwell Automation/Allen-Bradley recommends updating firmware: controllogix_controllers to greater than 19; guardlogix_controllers to greater than 20; softlogix_controllers to greater than 19; compactlogix_controllers to greater than 19.

See Also

https://www.us-cert.gov/ics/advisories/ICSA-13-011-03

Plugin Details

Severity: High

ID: 720000

Family: SCADA

Published: 5/8/2019

Updated: 9/30/2019

Risk Information

VPR

Risk Factor: Low

Score: 3.6

CVSS v2

Risk Factor: High

Base Score: 7.8

Temporal Score: 5.8

Vector: CVSS2#AV:N/AC:L/Au:N/C:N/I:N/A:C

Vulnerability Information

Patch Publication Date: 1/10/2013

Vulnerability Publication Date: 1/10/2013

Reference Information

CVE: CVE-2012-6435