Siemens RUGGEDCOM WIN Multiple Devices Reversible Password Storage

medium Nessus Network Monitor Plugin ID 720059

Synopsis

Siemens RUGGEDCOM WIN devices allow an attacker to discover password hashes.

Description

Siemens Ruggedcom WIN51xx devices with firmware before SS4.4.4624.35, WIN52xx devices with firmware before SS4.4.4624.35, WIN70xx devices with firmware before BS4.4.4621.32, and WIN72xx devices with firmware before BS4.4.4621.32 allow context-dependent attackers to discover password hashes by reading (1) files or (2) security logs.

Solution

Perform vendor recommended mitigations and apply available vendor upgrades.

See Also

http://www.siemens.com/innovation/pool/de/forschungsfelder/siemens_security_advisory_ssa-753139.pdf,https://ics-cert.us-cert.gov/advisories/ICSA-15-034-02

Plugin Details

Severity: Medium

ID: 720059

Family: SCADA

Published: 5/8/2019

Updated: 9/30/2019

Risk Information

VPR

Risk Factor: Medium

Score: 4.0

CVSS v2

Risk Factor: Medium

Base Score: 5

Temporal Score: 3.7

Vector: CVSS2#AV:N/AC:L/Au:N/C:P/I:N/A:N

Vulnerability Information

Patch Publication Date: 2/3/2015

Vulnerability Publication Date: 2/3/2015

Reference Information

CVE: CVE-2015-1357