Siemens SIMATIC S7-1200 and SIMATIC S7-1500 CPU < 2.6 TCP Connections DOS

high Nessus Network Monitor Plugin ID 720168

Synopsis

Siemens SIMATIC S7-1200 and S7-1500 CPUs are vulnerable to the denial-of-service (DOS) attack after opening multiple TCP connections.

Description

A vulnerability has been identified in SIMATIC S7-1200 (All versions), SIMATIC S7-1500 (All Versions < V2.6). An attacker could exhaust the available connection pool of an affected device by opening a sufficient number of connections to the device. Successful exploitation requires an attacker to be able to send packets to port 102/tcp of the affected device. No user interaction and no user privileges are required to exploit the vulnerability. The vulnerability, if exploited, could cause a Denial-of-Service condition impacting the availability of the system. At the time of advisory publication no public exploitation of this vulnerability was known.

Solution

Perform vendor recommended mitigations and apply available vendor upgrades.

See Also

http://www.securityfocus.com/bid/105928,https://cert-portal.siemens.com/productcert/pdf/ssa-584286.pdf

Plugin Details

Severity: High

ID: 720168

Family: SCADA

Published: 5/8/2019

Updated: 9/30/2019

Risk Information

VPR

Risk Factor: Low

Score: 3.6

CVSS v2

Risk Factor: Medium

Base Score: 5

Temporal Score: 3.7

Vector: CVSS2#AV:N/AC:L/Au:N/C:N/I:N/A:P

CVSS v3

Risk Factor: High

Base Score: 7.5

Temporal Score: 6.5

Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Temporal Vector: CVSS:3.0/E:U/RL:O/RC:C

Vulnerability Information

Patch Publication Date: 11/13/2018

Vulnerability Publication Date: 11/13/2018

Reference Information

CVE: CVE-2018-13815

BID: 105928