Siemens SIMATIC S7-1500 CPU Improper Input Validation (CVE-2018-16559)

high Tenable OT Security Plugin ID 500116

Synopsis

The remote OT asset is affected by a vulnerability.

Description

A vulnerability has been identified in SIMATIC S7-1500 CPU (All versions >= V2.0 and < V2.5), SIMATIC S7-1500 CPU (All versions <= V1.8.5). Specially crafted network packets sent to port 80/tcp or 443/tcp could allow an unauthenticated remote attacker to cause a Denial-of-Service condition of the device. The security vulnerability could be exploited by an attacker with network access to the affected systems on port 80/tcp or 443/tcp. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise availability of the device. At the time of advisory publication no public exploitation of this security vulnerability was known. This plugin only works with Tenable.ot. Please visit https://www.tenable.com/products/tenable-ot for more information.

Solution

The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original can be found at CISA.gov.

Siemens recommends users upgrade to Version 2.5 or newer. Users who cannot upgrade because of hardware restrictions are recommended to apply the manual mitigations. Updates are available for download from the following link:

https://support.industry.siemens.com/cs/de/en/view/109478459

Siemens also recommends users apply the following manual mitigations:

- Protect network access to Port 80/tcp and Port 443/tcp of affected devices.
- Apply cell protection concept.
- Apply defense-in-depth.

As a general security measure, Siemens strongly recommends protecting network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for Industrial Security (Download:
https://www.siemens.com/cert/operational-guidelines-industrial-security) and following the recommendations in the product manuals.

Additional information on industrial security for Siemens devices can be found at:

https://www.siemens.com/Industrialsecurity

For more information on these vulnerabilities and more detailed mitigation instructions, please see Siemens Security Advisory SSA-180635 at the following location:

http://www.siemens.com/cert/advisories

See Also

https://cert-portal.siemens.com/productcert/pdf/ssa-180635.pdf

https://www.cisa.gov/news-events/ics-advisories/icsa-19-036-04

Plugin Details

Severity: High

ID: 500116

Version: 1.8

Type: remote

Family: Tenable.ot

Published: 2/7/2022

Updated: 12/4/2024

Supported Sensors: Tenable OT Security

Risk Information

VPR

Risk Factor: Low

Score: 3.6

CVSS v2

Risk Factor: High

Base Score: 7.8

Temporal Score: 5.8

Vector: CVSS2#AV:N/AC:L/Au:N/C:N/I:N/A:C

CVSS Score Source: CVE-2018-16559

CVSS v3

Risk Factor: High

Base Score: 7.5

Temporal Score: 6.5

Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Temporal Vector: CVSS:3.0/E:U/RL:O/RC:C

Vulnerability Information

CPE: cpe:/o:siemens:simatic_s7-1500_firmware

Required KB Items: Tenable.ot/Siemens

Exploit Ease: No known exploits are available

Patch Publication Date: 4/17/2019

Vulnerability Publication Date: 4/17/2019

Reference Information

CVE: CVE-2018-16559

CWE: 20

ICSA: 19-036-04