Siemens SIPROTEC 4, SIPROTEC Compact, DIGSI 4, and EN100 Ethernet Module Missing Authentication For Critical Function (CVE-2018-4840)

high Tenable OT Security Plugin ID 500119

Synopsis

The remote OT asset is affected by a vulnerability.

Description

A vulnerability has been identified in DIGSI 4 (All versions < V4.92), EN100 Ethernet module DNP3 variant (All versions < V1.05.00), EN100 Ethernet module IEC 104 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.30), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). The device engineering mechanism allows an unauthenticated remote user to upload a modified device configuration overwriting access authorization passwords.

This plugin only works with Tenable.ot. Please visit https://www.tenable.com/products/tenable-ot for more information.

Solution

The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original can be found at CISA.gov.

Siemens has provided the following updates for mitigations:

- DIGSI 4: Update to v4.92.
- EN100 Ethernet module IEC 61850 variant: Update to v4.30.

- EN100 Ethernet module DNP3 variant: Update to v4.30 and configure DIGSI 4 connection password.

- SIPROTEC Compact 7SJ80: Update to v4.77.
- SIPROTEC Compact 7SK80: Update to v4.77.
- SIPROTEC 4 7SJ61, 7SJ62, and 7SJ64: Update to v4.96.
- SIPROTEC 4 7SJ66: Update to v4.30.
- SIPROTEC 4 7SD80: Update to v4.70.

As a general security measure, Siemens strongly recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens operational guidelines for Industrial Security and following the recommendations in the product manuals.

Recommended security guidelines to secure substations and defense in depth can be found at:
https://www.siemens.com/gridsecurity.

For more information on these vulnerabilities and associated software updates, please see Siemens security advisory SSA-203306

See Also

https://cert-portal.siemens.com/productcert/pdf/ssa-203306.pdf

https://ics-cert.us-cert.gov/advisories/ICSA-18-067-01

Plugin Details

Severity: High

ID: 500119

Version: 1.7

Type: remote

Family: Tenable.ot

Published: 2/7/2022

Updated: 9/4/2024

Supported Sensors: Tenable OT Security

Risk Information

VPR

Risk Factor: Low

Score: 3.6

CVSS v2

Risk Factor: Medium

Base Score: 5

Temporal Score: 3.7

Vector: CVSS2#AV:N/AC:L/Au:N/C:N/I:P/A:N

CVSS Score Source: CVE-2018-4840

CVSS v3

Risk Factor: High

Base Score: 7.5

Temporal Score: 6.5

Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N

Temporal Vector: CVSS:3.0/E:U/RL:O/RC:C

Vulnerability Information

CPE: cpe:/o:siemens:siprotec_4_7sj66_firmware, cpe:/o:siemens:siprotec_compact_7sk80_firmware, cpe:/o:siemens:en100_ethernet_module_iec_104_firmware:-, cpe:/o:siemens:digsi_4, cpe:/o:siemens:siprotec_compact_7sj80_firmware, cpe:/o:siemens:en100_ethernet_module_profinet_io_firmware:-, cpe:/o:siemens:en100_ethernet_module_modbus_tcp_firmware:-, cpe:/o:siemens:en100_ethernet_module_iec_61850_firmware, cpe:/o:siemens:en100_ethernet_module_dnp3_firmware:-

Required KB Items: Tenable.ot/Siemens

Exploit Ease: No known exploits are available

Patch Publication Date: 3/8/2018

Vulnerability Publication Date: 3/8/2018

Reference Information

CVE: CVE-2018-4840

CWE: 306

ICSA: 18-067-01