Siemens Desigo PXC and DXR Devices Improper Restriction of Excessive Authentication Attempts (CVE-2022-24044)

high Tenable OT Security Plugin ID 500730

Synopsis

The remote OT asset is affected by a vulnerability.

Description

A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.142.5-22), Desigo PXC3 (All versions < V01.21.142.4-18), Desigo PXC4 (All versions < V02.20.142.10-10884), Desigo PXC5 (All versions < V02.20.142.10-10884). The login functionality of the application does not employ any countermeasures against Password Spraying attacks or Credential Stuffing attacks. An attacker could obtain a list of valid usernames on the device by exploiting the issue and then perform a precise Password Spraying or Credential Stuffing attack in order to obtain access to at least one account.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

Solution

The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original can be found at CISA.gov.

Siemens recommends updating to the latest software version:

- Desigo DXR2: Update to v01.21.142.5-22 or later
- Desigo PXC3: Update to v01.21.142.4-18 or later
- Desigo PXC4: Update to v02.20.142.10-10884 or later
- Desigo PXC5: Update to v02.20.142.10-10884 or later

Contact Siemens for update information.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following the recommendations in the product manuals.

For additional information, please refer to Siemens Security Advisory SSA-626968

For additional information, please refer to Siemens Security Advisory SSA-662649

See Also

https://cert-portal.siemens.com/productcert/pdf/ssa-626968.pdf

https://www.cisa.gov/news-events/ics-advisories/icsa-22-132-10

Plugin Details

Severity: High

ID: 500730

Version: 1.5

Type: remote

Family: Tenable.ot

Published: 1/25/2023

Updated: 9/4/2024

Supported Sensors: Tenable OT Security

Risk Information

VPR

Risk Factor: Low

Score: 3.6

CVSS v2

Risk Factor: Medium

Base Score: 5

Temporal Score: 3.7

Vector: CVSS2#AV:N/AC:L/Au:N/C:P/I:N/A:N

CVSS Score Source: CVE-2022-24044

CVSS v3

Risk Factor: High

Base Score: 7.5

Temporal Score: 6.5

Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N

Temporal Vector: CVSS:3.0/E:U/RL:O/RC:C

Vulnerability Information

CPE: cpe:/o:siemens:desigo_dxr2_firmware, cpe:/o:siemens:desigo_pxc3_firmware, cpe:/o:siemens:desigo_pxc5_firmware, cpe:/o:siemens:desigo_pxc4_firmware

Required KB Items: Tenable.ot/Siemens

Exploit Ease: No known exploits are available

Patch Publication Date: 5/20/2022

Vulnerability Publication Date: 5/20/2022

Reference Information

CVE: CVE-2022-24044

CWE: 307

ICSA: 22-132-10