Schneider Electric Modicon M221 Information Management Errors (CVE-2018-7790)

critical Tenable OT Security Plugin ID 500858

Synopsis

The remote OT asset is affected by a vulnerability.

Description

An Information Management Error vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to replay authentication sequences. If an attacker exploits this vulnerability and connects to a Modicon M221, the attacker can upload the original program from the PLC.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

Solution

The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original can be found at CISA.gov.

A fix for these vulnerabilities is implemented in Modicon M221 Firmware v1.6.2.0, delivered within SoMachine Basic v1.6 SP2, which is available for download below, or by using Schneider Electric Software Update tool:

https://www.schneider-electric.com/en/download/document/SoMachineBasicV1.6SP2/

As a temporary mitigation, Modicon M221 users should take the following measures:

- Set up a firewall blocking all remote/external access to Port 502.
- Within the Modicon M221 application, users must disable all unused protocols, especially programming protocol, as described in section “Configuring Ethernet Network” of SoMachine Basic online help. This will prevent remote programming of the M221 PLC.

Schneider Electric’s security notice SEVD-2018-235-01 is available at the following location:

https://www.schneider-electric.com/en/download/document/SEVD-2018-235-01/

See Also

http://www.securityfocus.com/bid/105182

https://www.cisa.gov/news-events/ics-advisories/icsa-18-240-01

http://www.nessus.org/u?f8a96d9c

Plugin Details

Severity: Critical

ID: 500858

Version: 1.9

Type: remote

Family: Tenable.ot

Published: 3/1/2023

Updated: 9/4/2024

Supported Sensors: Tenable OT Security

Risk Information

VPR

Risk Factor: Medium

Score: 5.9

CVSS v2

Risk Factor: High

Base Score: 7.5

Temporal Score: 5.5

Vector: CVSS2#AV:N/AC:L/Au:N/C:P/I:P/A:P

CVSS Score Source: CVE-2018-7790

CVSS v3

Risk Factor: Critical

Base Score: 9.8

Temporal Score: 8.5

Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

Temporal Vector: CVSS:3.0/E:U/RL:O/RC:C

Vulnerability Information

CPE: cpe:/o:schneider-electric:modicon_m221_series_firmware

Required KB Items: Tenable.ot/Schneider

Exploit Ease: No known exploits are available

Patch Publication Date: 8/29/2018

Vulnerability Publication Date: 8/29/2018

Reference Information

CVE: CVE-2018-7790

CWE: 294

ICSA: 18-240-01