Hitachi Energy's RTU500 series Unrestricted Upload of File with Dangerous Type (CVE-2024-1532)

medium Tenable OT Security Plugin ID 502225

Synopsis

The remote OT asset is affected by a vulnerability.

Description

A vulnerability exists in the stb-language file handling that affects the RTU500 series product versions listed below. A malicious actor could enforce diagnostic texts being displayed as empty strings, if an authorized user uploads a specially crafted stb-language file.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

Solution

The following text was originally created by the Cybersecurity and Infrastructure Security Agency (CISA). The original can be found at CISA.gov.

Hitachi Energy has released the following mitigations for CVE-2024-1532 and CVE-2024-1532:

- RTU500 series CMU Firmware Version 12.7.1 - 12.7.6: Update to CMU Firmware Version 12.7.7
- RTU500 series CMU Firmware Version 13.2.1 - 13.2.6: Update to CMU Firmware Version 13.2.7

Until the updates are made available, Hitachi Energy recommends the following general mitigation factors/workarounds for the products with RTU500 series CMU firmware Versions 12.0.1 - 12.0.14, 12.2.1 - 12.2.11, 12.4.1 - 12.4.11, 12.6.1 - 12.6.9, 13.4.1 - 13.4.4, and 13.5.1 - 13.5.3 to address the vulnerabilities CVE-2024-1532 and CVE-2024-1532:

- Recommended security practices and firewall configurations can help protect a process control network from attacks originating from outside the network including.
- Physically protect process control systems from direct access by unauthorized personnel.
- Do not allow process control systems direct connections to the Internet.
- Separate process control systems from other networks by means of a firewall system that has a minimal number of ports exposed.
- Process control systems should not be used for Internet surfing, instant messaging, or receiving emails.
- Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.

For more information, see Hitachi Energy's Security Advisories.

See Also

http://www.nessus.org/u?eea04659

https://www.cisa.gov/news-events/ics-advisories/icsa-24-116-01

Plugin Details

Severity: Medium

ID: 502225

Version: 1.3

Type: remote

Family: Tenable.ot

Published: 5/2/2024

Updated: 9/4/2024

Supported Sensors: Tenable OT Security

Risk Information

VPR

Risk Factor: Medium

Score: 4.4

CVSS v3

Risk Factor: Medium

Base Score: 6.8

Temporal Score: 5.9

Vector: CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:C/C:N/I:N/A:H

Temporal Vector: CVSS:3.0/E:U/RL:O/RC:C

Vulnerability Information

CPE: cpe:/o:hitachienergy:rtu500_firmware

Required KB Items: Tenable.ot/ABB

Exploit Ease: No known exploits are available

Vulnerability Publication Date: 3/26/2024

Reference Information

CVE: CVE-2024-1532

CWE: 434

ICSA: 24-116-01