Siemens SCALANCE X-200RNA Switch Devices Use After Free (CVE-2015-6564)

high Tenable OT Security Plugin ID 503131

Synopsis

The remote OT asset is affected by a vulnerability.

Description

Use-after-free vulnerability in the mm_answer_pam_free_ctx function in monitor.c in sshd in OpenSSH before 7.0 on non-OpenBSD platforms might allow local users to gain privileges by leveraging control of the sshd uid to send an unexpectedly early MONITOR_REQ_PAM_FREE_CTX request.

This plugin only works with Tenable.ot.
Please visit https://www.tenable.com/products/tenable-ot for more information.

Solution

Refer to the vendor advisory.

See Also

https://cert-portal.siemens.com/productcert/pdf/ssa-412672.pdf

https://support.industry.siemens.com/cs/ww/en/view/109814809/

https://www.cisa.gov/news-events/ics-advisories/icsa-22-349-21

Plugin Details

Severity: High

ID: 503131

Version: 1.1

Type: remote

Family: Tenable.ot

Published: 3/13/2025

Updated: 3/13/2025

Supported Sensors: Tenable OT Security

Risk Information

VPR

Risk Factor: Medium

Score: 5.9

CVSS v3

Risk Factor: High

Base Score: 7.4

Temporal Score: 6.7

Vector: CVSS:3.0/AV:L/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H

Temporal Vector: CVSS:3.0/E:P/RL:O/RC:C

Vulnerability Information

CPE: cpe:/o:siemens:scalance_x204rna_%28hsr%29_firmware:3.2.7, cpe:/o:siemens:scalance_x204rna_eec_%28prp%29_firmware:3.2.7, cpe:/o:siemens:scalance_x204rna_eec_%28prp%2fhsr%29_firmware:3.2.7, cpe:/o:siemens:scalance_x204rna_%28prp%29_firmware:3.2.7, cpe:/o:siemens:scalance_x204rna_eec_%28hsr%29_firmware:3.2.7

Required KB Items: Tenable.ot/Siemens

Exploit Ease: No known exploits are available

Patch Publication Date: 12/13/2022

Vulnerability Publication Date: 12/13/2022

Reference Information

CVE: CVE-2015-6564

CWE: 416

ICSA: 22-349-21